Previous Next VCB 12KV Indoor Type Switch Gear Panel (12 Outgoings) (VCB)(Withdrawable Type) Electrical Component COUNTRY OF ORIGIN(Japan, Korea, Europe)Rated Voltage – 12kVRated Current – 630ABreaking capacity – 25kA, rmsMaking Current – 62.5kAInsulation level – 28kV RMS/1 MinControl Voltage – 110V DCSpring charging – 230 VACClosing & Tripping control voltage – 110V DC Discreapancy Switches Indication Lamp – on/off, Over current, Earth fault Alarm system for relay & gas pressure low CB, Position indicator,Healthy trip etc. Complete internal wiring diagram (Mounted on panel) AD, DC Protection Fuse Overcurrent Relay Type – Inverse TypePrinciple – NumericalRated input – AC 5A , 50HzCurrent setting range – 10% to 200%Inverse time unit – .025 – 1 xtInstantaneous unit – 50% to 1600% Earth Fault Relay Type – Inverse TypePrinciple – NumbericalRated input – AC 5A , 50HzCurrent setting range – 5% to 50%Inverse time unit – .025 – 1 xtInstantaneous unit – 20% to 200% Current Transformer Rated Voltage – 12KVShort Time withstand Current – 25kA rmsCT Ratio – 150-300/5/5 ABurden – 30VAAccuracy Class – 0.5 CL/ 5P10/ 5P10 Metering Digital Voltmeter0 – 15kVDigital Ammeter0 – 150/300/5ALoad Manager – To Read V,A,F, Power, Power Factor, Harmonics Com : Port: RS 485Energy Meter – 3 Ph, 3 Wire, 110V , 5A